<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>Blow down Archives - Chemical Engineering Site</title>
	<atom:link href="https://chemicalengineeringsite.in/tag/blow-down/feed/" rel="self" type="application/rss+xml" />
	<link>https://chemicalengineeringsite.in/tag/blow-down/</link>
	<description>For Chemical Engineers</description>
	<lastBuildDate>Sat, 03 Sep 2022 09:41:26 +0000</lastBuildDate>
	<language>en-US</language>
	<sy:updatePeriod>
	hourly	</sy:updatePeriod>
	<sy:updateFrequency>
	1	</sy:updateFrequency>
	<generator>https://wordpress.org/?v=6.9.4</generator>
	<item>
		<title>Cooling Tower Efficiency Calculations</title>
		<link>https://chemicalengineeringsite.in/cooling-tower-efficiency-calculations/</link>
					<comments>https://chemicalengineeringsite.in/cooling-tower-efficiency-calculations/#respond</comments>
		
		<dc:creator><![CDATA[chemicalengineeringsite]]></dc:creator>
		<pubDate>Sat, 22 Oct 2016 12:55:08 +0000</pubDate>
				<category><![CDATA[Industry]]></category>
		<category><![CDATA[Process Design]]></category>
		<category><![CDATA[Blow down]]></category>
		<category><![CDATA[Cooling Tower]]></category>
		<category><![CDATA[Cooling Tower Approach]]></category>
		<category><![CDATA[Cooling Tower Make up water]]></category>
		<category><![CDATA[Cooling Tower Range]]></category>
		<category><![CDATA[Cycle of Concentration]]></category>
		<category><![CDATA[Drift Loss]]></category>
		<category><![CDATA[Evaporation Loss]]></category>
		<guid isPermaLink="false">http://chemicalengineeringsite.in/?p=58</guid>

					<description><![CDATA[<p>Get unlimited access to 5,000+ magazines, newspapers and curated premium stories at flat 55% off Cooling Tower Efficiency Calculation is described in this article. Cooling Tower plays a major role in Chemical Process Industry. They reject process heat from the cooling water to atmosphere and keep the water cool. The performance of the cooling tower [&#8230;]</p>
<p>The post <a href="https://chemicalengineeringsite.in/cooling-tower-efficiency-calculations/">Cooling Tower Efficiency Calculations</a> appeared first on <a href="https://chemicalengineeringsite.in">Chemical Engineering Site</a>.</p>
]]></description>
										<content:encoded><![CDATA[
<a href="https://www.kqzyfj.com/click-100252325-14091100" target="_blank" rel="noopener noreferrer"> Get unlimited access to 5,000+ magazines, newspapers and curated premium stories at flat 55% off </a><img decoding="async" src="https://www.tqlkg.com/image-100252325-14091100" width="1" height="1" border="0">


<p>Cooling Tower Efficiency Calculation is described in this article. <a href="http://chemicalengineeringsite.in/tag/cooling-tower/">Cooling Tower</a> plays a major role in Chemical Process Industry. They reject process heat from the cooling water to atmosphere and keep the water cool. The performance of the cooling tower depends on various parameters like Range &amp; Approach. We shall see those terminologies in Detail.</p>
<h2>Cooling Tower&nbsp;Approach</h2>
<p>The difference between the Cold Water Temperature (Cooling Tower Outlet)</p>
<p>And ambient Wet Bulb Temperature is called as Cooling Tower Approach.</p>
<p><strong><em>&nbsp;Approach = Cold Water Temperature – Wet Bulb Temperature</em></strong></p>
<p>Cooling Tower approach is the better indicator of the performance.</p>
<h2>Cooling Tower Range</h2>
<p>The difference between the Hot Water Temperature (Cooling Tower Inlet) Temperature and Cold water (Cooling Tower Outlet) temperature is called Cooling Tower Range.</p>
<p><em><strong>Range = Hot Water Temperature – Cold Water Temperature</strong></em></p>
<p><img fetchpriority="high" decoding="async" class="size-full wp-image-59 alignleft" src="http://chemicalengineeringsite.in/wp-content/uploads/2016/10/Cooling-Tower-Efficiency.jpg" alt="Cooling Tower Efficiency" width="675" height="795" srcset="https://chemicalengineeringsite.in/wp-content/uploads/2016/10/Cooling-Tower-Efficiency.jpg 675w, https://chemicalengineeringsite.in/wp-content/uploads/2016/10/Cooling-Tower-Efficiency-255x300.jpg 255w" sizes="(max-width: 675px) 100vw, 675px" /></p>
<h2>Cooling Tower Efficiency Calculation</h2>
<p>The calculation of cooling tower efficiency involves the Range and approach of the cooling Tower. Cooling tower efficiency is limited by the ambient wet bulb temperature. In the ideal case, the cold water temperature will be equal to the wet-bulb temperature. This is practically not possible to achieve. This requires very large tower and results in huge evaporation and windage or drift loss resulting in a practically not viable solution. In practice, the cooling tower efficiency will be in between 70 to 75%.</p>
<p><strong><em>Cooling Tower Efficiency =&nbsp;&nbsp;&nbsp;&nbsp;</em></strong></p>
<p><strong><em>(Hot Water Temperature – Cold water Temperature) x 100/</em></strong></p>
<p><strong><em>(Hot Water&nbsp;Temperature – Wet bulb temperature)</em></strong></p>
<p>Or Simply</p>
<p><em><strong>Cooling Tower Efficiency = Range/ (Range + Approach) x 100</strong></em></p>
<p>In summer the ambient air wet bulb temperature raises when compared to winter thus limiting the cooling tower efficiency.</p>
<h2>Other Cooling Tower Calculations</h2>
<p>This includes determination of cycle of concentration, Evaporation loss, Drift or Windage Loss, Blow down water requirement makeup water requirement.</p>
<h3>Cycle of Concentration</h3>
<p>The cycle of concentration is a dimensionless number. It is a ratio between parameter in Cooling Water to the parameter in Makeup water. It can be calculated from any the following formulae.</p>
<p>COC= Silica in Cooling Water / Silica in Makeup Water</p>
<p>COC = Ca Hardness in Cooling Water/ Ca Hardness in Makeup water</p>
<p>COC = Conductivity of Cooling Water / Conductivity of Makeup water</p>
<p>The cycle of concentration normally varies from 3.0 to 7.0 depending on the Process Design. It is advisable to keep the Cycle of concentration as high as possible to reduce the makeup water requirement of the cooling tower. At the same time, the higher cycle of concentration increases the dissolved solids concentration in circulating cooling water which results in scaling and fouling of process heat transfer equipment.</p>
<h3>Draw off or Blowdown</h3>
<p>As the cooling water circulates the cooling tower part of water evaporates thereby increasing the total dissolved solids in the remaining water. To control the Cycle of Concentration blow down is given. Blowdown is the function of Cycle of concentration. Blowdown can be calculated from the formula:</p>
<p>B = E/ (COC-1)</p>
<p>B = Blow Down (m<sup>3</sup>/hr)</p>
<p>E = Evaporation Loss (m<sup>3</sup>/hr)</p>
<p>COC = Cycle of Concentration. Varies from 3.0 to 7.0 depending upon Manufactures Guidelines</p>
<h3>Evaporation Loss Calculation</h3>
<p>Evaporation Loss in the cooling tower is calculated by the following empirical equation.</p>
<p><em><strong>E = 0.00085 x R x 1.8 x C</strong></em></p>
<p>E = Evaporation Loss (m<sup>3</sup>/hr)</p>
<p>R= Range</p>
<p>C = Circulating Cooling Water (m<sup>3</sup>/hr)</p>
<p>(Reference: Perry’s Chemical Engineers Hand Book )</p>
<p>Alternatively, The Evaporation loss can be calculated from the heat balance across the cooling tower. The amount of heat to be removed from Circulating water according to <em><strong>Q = &nbsp;m&nbsp;C<sub>p&nbsp;&nbsp;</sub>DT is&nbsp;</strong><strong>C x C<sub>p&nbsp;</sub>x R <sub>. &nbsp;</sub></strong></em>The amount of heat removed by evaporative cooling is&nbsp;<em><strong>Q = m x&nbsp;Hv is&nbsp;E&nbsp;x&nbsp;H<sub>V</sub></strong></em></p>
<p>On Equating these two, we get</p>
<p><em><strong>E = C x R x C<sub>p </sub>/ H<sub>V</sub></strong></em></p>
<p>E = Evaporation Loss in m<sup>3</sup>/hr</p>
<p>C= Cycle of Concentration</p>
<p>R= Range in °C</p>
<p>Cp&nbsp;= Specific Heat = 4.184 kJ / kg / °C</p>
<p>H<sub>V</sub>&nbsp;= Latent heat of vaporization = 2260 kJ / kg</p>
<h3>Windage or Drift Loss Calculation</h3>
<p>Drift loss of the cooling tower is normally provided by the cooling tower manufacturer based on the Process design. If it is not available it may be assumed as</p>
<p>For Natural Draft Cooling Tower <strong><em>D = 0.3 to 1.0 * C /100</em></strong></p>
<p>For Induced Draft Cooling Tower<em><strong> D = 0.1 to 0.3 * C /100</strong></em></p>
<p>For Cooling Tower with Drift Eliminator <em><strong>D = 0.01* C /100</strong></em></p>
<h3>Cooling Tower Mass Balance – makeup water</h3>
<p><img decoding="async" class="wp-image-60 alignnone" src="http://chemicalengineeringsite.in/wp-content/uploads/2016/10/Cooling-Tower-Calculations.jpg" alt="Cooling Tower Calculations" width="653" height="669" srcset="https://chemicalengineeringsite.in/wp-content/uploads/2016/10/Cooling-Tower-Calculations.jpg 1005w, https://chemicalengineeringsite.in/wp-content/uploads/2016/10/Cooling-Tower-Calculations-293x300.jpg 293w, https://chemicalengineeringsite.in/wp-content/uploads/2016/10/Cooling-Tower-Calculations-768x786.jpg 768w, https://chemicalengineeringsite.in/wp-content/uploads/2016/10/Cooling-Tower-Calculations-1000x1024.jpg 1000w" sizes="(max-width: 653px) 100vw, 653px" /></p>
<p>Cooling tower mass balance gives an idea about make-up water requirement. Cooling Tower Makeup has to substitute the water losses resulting from Evaporation, Windage and Blowdown.</p>
<p><em><strong>M = E + D + B</strong></em></p>
<p>M = Make up water Requirement&nbsp;in m<sup>3</sup>/hr</p>
<p>B = Blow Down&nbsp;in m<sup>3</sup>/hr</p>
<p>E = Evaporation Loss &nbsp;in m<sup>3</sup>/hr</p>
<p>D = Drift Loss in m<sup>3</sup>/hr</p>
<p></p>
<p>Have you learned about Cooling Tower Calculations? It&#8217;s time to test your knowledge on Cooling towers. Take our <a href="http://chemicalengineeringsite.in/test-knowledge-cooling-tower-online-quiz/">Online Quiz on Cooling towers</a> now.</p>
<p></p>
<p><span style="font-size: inherit;">More Articles of Chemical Engineering Site:</span></p>
<p><a class="entry-title-link" href="http://chemicalengineeringsite.in/test-your-knowledge-on-steam-turbines-online-quiz/" rel="bookmark">Test Your knowledge on Steam Turbines – Online Quiz</a></p>
<p><a class="entry-title-link" href="http://chemicalengineeringsite.in/test-knowledge-boilers-online-quiz/" rel="bookmark">Test Your knowledge on Boilers – Online Quiz</a></p>
<p><a class="entry-title-link" href="http://chemicalengineeringsite.in/piping-and-instrumentation-diagram-pid/" rel="bookmark">Piping and Instrumentation Diagram – P&amp;ID</a>&nbsp;&#8211; With Excel Checklist</p>
<p><a class="entry-title-link" href="http://chemicalengineeringsite.in/confined-space-online-quiz/" rel="bookmark">Test Your knowledge on Confined Space – Online Quiz</a></p>
<p></p>


<a href="https://click.linksynergy.com/fs-bin/click?id=4RFVIcKOqhI&amp;offerid=742306.786&amp;type=4&amp;subid=0&amp;LSNSUBSITE=LSNSUBSITE"><img decoding="async" alt="Edureka - Edureka - Month End Offer-Flat 30% OFF ON Live Course" border="0" src="https://cdn2.hubspot.net/hubfs/493391/Affiliate/ME_Live_240x400.png"></a><img loading="lazy" decoding="async" border="0" width="1" height="1" src="https://ad.linksynergy.com/fs-bin/show?id=4RFVIcKOqhI&amp;bids=742306.786&amp;type=4&amp;subid=0">



<iframe loading="lazy" width="540" height="655" src="https://0d45638c.sibforms.com/serve/MUIEAMk9gENHskJPjnn-caN3uxUNsXFA0H9EXeJmmA2Z0viTTjtdg0l9btD7X77Dn2y_VxBzTGYXfxoGtGJeu4mV0254zc9lswbEmYC5CLfxsVLJAK8TjuoCEADIw3BWL80138UxCiR5MlDLMuH0VSM2FiTbVFfQd5qJQs7PDxllgI0oaO0DomSWh7a11DHMp26alQbySqRiXjsr" frameborder="0" scrolling="auto" allowfullscreen="" style="display: block;margin-left: auto;margin-right: auto;max-width: 100%;"></iframe>
<p>The post <a href="https://chemicalengineeringsite.in/cooling-tower-efficiency-calculations/">Cooling Tower Efficiency Calculations</a> appeared first on <a href="https://chemicalengineeringsite.in">Chemical Engineering Site</a>.</p>
]]></content:encoded>
					
					<wfw:commentRss>https://chemicalengineeringsite.in/cooling-tower-efficiency-calculations/feed/</wfw:commentRss>
			<slash:comments>0</slash:comments>
		
		
			</item>
	</channel>
</rss>